Low-voltage systems for NYC mixed-use developments: base building, apartments and tenants
How the cameras, entry, access control, cabling and networks of a new mixed-use building divide between the developer, the residents and each commercial tenant, and how the telecom room and the riser keep them apart.
Technical figures checked against the standards listed at the end.
Low-voltage systems in a NYC mixed-use building split three ways: base building systems the developer installs and the building runs after turnover (the entry intercom, common-area cameras, access control on the building doors, the main telecom room and the risers), cabling from that room to a panel in every apartment, and tenant systems each store or office installs inside its own space. The plan that works gives each owner its own backboard or rack in the cellar telecom room, its own sleeves up the riser and its own network, and writes down, before the slabs are poured, exactly where the developer's work ends and each tenant's begins.
Mixed-use problems tend to sit at the seams between owners: a store with no pathway to the cellar, a riser filled by the first carrier to arrive, an intercom that calls every apartment but not the office upstairs, a store's laptop on the same network as the lobby cameras. This guide works through one example building to show how the systems divide, how the MDF and the riser keep them apart, and who does what from design to turnover.
Every figure uses the same example: a new eight-story mixed-use building in Brooklyn. The cellar holds the main telecom room, the MDF. The ground floor has two stores beside the residential lobby, the second floor is an office or medical suite, and floors 3 to 8 hold 48 apartments, eight to a floor. It is an example, not a client's building.
01Low-voltage systems in a mixed-use building: three owners, one building
A mixed-use building is several buildings sharing a cellar, a riser and often a front door. Its low-voltage work divides by who pays for each system and who runs it once the developer hands the building over. Figure 1 shows the example building one owner at a time; the last view rings the five places where one owner's work ends and the next begins.
Swipe the drawing sideways to see the whole building.
Base building systems
These systems outlive every tenant. No tenant or resident should be able to reach their network.
- Includes
- The lobby entry panel, cameras in the lobby, corridors and elevator cab, access control on the building doors and the roof door, and the MDF and risers themselves
- Pathway
- Its own rack in the MDF and its own sleeves up the riser, with a branch to each corridor
- After turnover
- The condo board, co-op board or landlord, usually through the managing agent
- Hands off at
- The lobby panel that calls the apartments, and the building doors that tenants also use
Base building systems
These serve the whole building and outlive every tenant: the entry panel at the lobby door, cameras in the lobby, the package room, corridors, stairs and the elevator cab, access control on the building doors and the roof door, and the MDF and risers that carry everything else. The developer pays for them as part of the base building. After turnover the condo board, co-op board or landlord runs them, usually through the managing agent. The cab camera reaches the car through the elevator's traveling cable or a wireless link, planned with the elevator contractor.
In a residential building with eight or more apartments built or converted after 1968, New York's Multiple Dwelling Law, section 50-a, calls for self-closing, self-locking entrance doors and an intercom that lets residents talk with visitors and release the door. The residential part of a mixed-use building is usually covered. Our guide to NYC building security rules covers this as general information, not legal advice.
Apartment cabling
The apartments need cable from the MDF to a panel in each unit, where internet, TV and the intercom arrive, and outlets from that panel to the rooms. The residential cabling standard, ANSI/TIA-570, plans for that panel in every unit and calls it a distribution device. The developer installs the cable, the building owns it up to the panel, and residents choose a provider and own whatever they plug in. Providers either light service over the cable the building installed or pull their own fiber through the same sleeves, so the residential riser needs room for both.
Store and office tenant systems
Stores and offices fit out their own spaces under their leases: register and card terminal drops, the store's own cameras and recorder, Wi-Fi, music, workstation cabling, a reader on the suite door. The developer's job is to leave a way in: a backboard for each tenant in the MDF, a sleeve from that backboard into the tenant's space, and power where the tenant's cabinet will sit. A ground floor store is often fed straight up through the cellar ceiling and never touches the riser. Our article on low-voltage services for a retail build-out covers the store side, including the landlord's work letter.
The five handoff points
- The carrier entrance. Provider fiber ends here, at what is often called the minimum point of entry; the building provides the conduit, the room and the backboard.
- Each tenant backboard. The building's work ends at the tenant's board in the MDF, with the carrier's line landed on it.
- The apartment panel. The building's cable ends there; the resident's router and devices start there.
- The suite door. The tenant's reader controls the suite, but its staff also use the building's street door. One credential for both is a deliberate link, not a default.
- The lobby panel. It calls every apartment, and calls the office reception only if that was planned.
Each of these sits between two contracts. Name the owner of each in both.
02The MDF, IDFs and separate pathways
The MDF, or main distribution frame, is the building's main telecom room, usually in the cellar near where the carriers enter. IDFs, intermediate distribution frames, are smaller closets on the floors served from it. In a mixed-use building the MDF holds every owner's equipment in one locked room, so it is laid out the way the building is owned:
- The carriers' entrance, where provider fiber comes in from the street through its own conduit.
- A backboard for the apartments, where the cable to every unit lands and providers connect.
- A backboard for each store and office, with the carrier's line for that tenant and a sleeve to its space.
- The base building's own racks: the camera recorder, door controllers, intercom equipment, the building's switch and a UPS, with clear space in front to work.
- A ground bar bonded to the building's grounding system, as ANSI/TIA-607 lays out, so every rack and backboard has a bonding point.
The room belongs to the building. Carriers and tenants' contractors get in on the building's terms, and the base building racks can sit in their own locked cabinet, so a carrier visit does not mean access to the recorder. A cellar MDF should also sit clear of water lines overhead and of any area that takes water in a storm.
Home runs from the cellar or a closet on each floor
The biggest pathway decision is where the apartment cables start. Home runs from the cellar put every apartment cable in the riser: simple, every cable in one room, no active equipment upstairs. A closet on each residential floor shrinks the riser to a fiber and a copper cable per floor, but every closet needs space, a dedicated circuit, cooling and a switch that someone has to maintain. Either way each copper run stays within the 90 m permanent link of ANSI/TIA-568; our site security planning guide walks through that riser length check, and in a tall building or one with long floors it may make the decision for you. Figure 2 sizes the sleeves for both choices.
Swipe the drawing sideways to see the sleeves.
Every apartment cable passes the cellar ceiling and the first two slabs. No active equipment upstairs.
Area: Cat6 0.049 sq in · coax 0.057 sq in · sleeve 12.57 sq in, limit 5.03 sq in
Sizing the riser sleeves
The arithmetic in Figure 2 is short. A 4-inch sleeve taken at 4.0 inches inside has 12.57 square inches of area, and 40 percent of that is 5.03 square inches. That is the fill NEC Chapter 9, Table 1, uses for conduit holding three or more cables, and a common design limit for sleeves. A Cat6 cable 0.25 inch across takes 0.049 square inch; an RG6 coax 0.27 inch across takes 0.057.
With home runs, 48 apartments with two Cat6 and one coax each put 96 Cat6 and 48 coax through the cellar ceiling: 7.46 square inches, more than one sleeve can take, so two sleeves at about 30 percent each. The base building's 26 cables fit one sleeve at about 10 percent. Add a spare to each riser pathway and one sleeve each for the office and the two stores, and the cellar ceiling needs 8 sleeves. With a closet on each floor instead, the apartments riser carries 12 cables in one sleeve, in exchange for six closets upstairs.
A sleeve set in the slab during construction is a line on a drawing. A sleeve added after the building is occupied means coring a finished slab inside someone's space. Cable in the riser is riser-rated (CMR) or better, and cable above an air-handling plenum ceiling is plenum-rated (CMP). Each sleeve through a rated floor is sealed with a listed fire-stop system, and what a sleeve can carry is also limited by what that system is listed for. Every penetration we make through a fire-rated wall or floor is fire-stopped. Sleeves that will take new cable for years are better sealed with a re-enterable product than a permanent one.
Cable category matters too. Cat6 is the usual choice for new work; Cat6A carries 10 Gb/s the full 100 m channel and handles high-power PoE bundles better. Our article on Cat5e vs Cat6 vs Cat6A explains when each one is worth it, and our structured cabling work starts from a cable count like this one.
03Separate networks for each tenant type
One fiber in the street does not mean one network inside. Each owner in a mixed-use building runs its own network on its own provider account, and the building's security systems sit on one that no tenant or resident can reach.
| Network | Owned and run by | What is on it |
|---|---|---|
| Base building | The board or landlord, through the managing agent | Cameras and the recorder, door controllers, the intercom, common-area Wi-Fi |
| Apartments | Each resident, with the provider they choose | The resident's router, computers, phones and TVs |
| Stores | Each store | Card terminals and registers, the store's cameras, its Wi-Fi and music |
| Office or medical suite | The tenant | Workstations, phones, Wi-Fi, the suite's readers and cameras |
Separate switches or VLANs
Separate switches and separate provider circuits are the clearest separation and the easiest to hand over: one owner, one box. Where one switch carries more than one network, each gets its own VLAN, a firewall decides what may cross, and the building, not a tenant, controls that switch. Either way, cameras and door controllers should not be reachable straight from the internet; remote viewing goes through a secure method the building controls. Networking for multi-tenant buildings covers how we set this up.
Stores that take cards, and medical suites
A store that takes payment cards answers to the card industry's security standard, PCI DSS. The standard does not require network segmentation, but it treats isolating the card systems from everything else as the way to shrink what has to be assessed. That is one more reason a store's network shares nothing with the building's or the next store's. A medical tenant usually separates clinical, office and guest traffic inside its own suite as well; our guide to planning cabling for an office or medical build-out covers that split.
Where systems have to talk
Separation has exceptions, and they should be designed rather than discovered: the lobby panel calling the office reception, an office tenant's staff using one credential at the street door and the suite door, a store's rear door on the building's access system for deliveries. Each one is a deliberate link between the base building and a tenant, written into both scopes. Our article on what access control is and how it works explains the parts involved, and how cabling infrastructure supports integrated security shows how cameras, readers and intercoms share one cable plant.
04Who does what: developer, GC, low-voltage contractor and tenants
On a new development the low-voltage scope touches at least six parties: the owner (the developer, then the board or landlord), the general contractor, the low-voltage contractor, the electrician, the carriers and the tenants. Figure 3 steps the example building through five phases and shows who does what for each part of the work. It is a typical split; your contracts decide the real one.
Before the slabs are poured. The owner decides what the building provides; the low-voltage design sets the room, the sleeve counts and the power list.
Swipe the table sideways to see every party.
| Part of the work | Owner or board | GC | Low voltage | Electrician | Carriers | Tenants |
|---|---|---|---|---|---|---|
| MDF room, backboards and riser sleeves | Decides | Sizes | Plans power | Advises | ||
| Carrier entrance and service | Requests | Advises | Survey | |||
| Base building cameras, entry and doors | Decides | Designs | ||||
| Cable to each apartment panel | Decides count | Designs | Advises | |||
| Inside each apartment | Decides outlets | Designs | ||||
| Store and office fit-outs | Writes work letter | Sizes sleeves | Plan | |||
| Power for low-voltage equipment | Lists circuits | Plans | ||||
| Fire-stopping of penetrations | Specifies | |||||
| Labels, tests, drawings, passwords | Requires |
Three rows in that matrix go wrong most often. Pathways: the GC builds the MDF room and sets sleeves in the slabs, but only to a drawing someone gave them. If the low-voltage design is not in the coordination set before the slabs are poured, the sleeves are sized by guess. Power: the electrician installs every circuit the racks, lock power supplies and intercom need, from a list the low-voltage contractor writes before rough-in; power for low-voltage equipment is coordinated with the electrician. Turnover: the building should receive the as-built drawings, a label and a test result for every cable, a device list with IP addresses and serial numbers, and every admin account and password, in writing, before the developer's team leaves.
What a tenant's work letter should say
A store or office lease usually comes with a work letter that splits the fit-out between landlord and tenant. For low voltage it should name the backboard and sleeve the tenant gets, the carrier line run to that backboard, the power provided for the tenant's cabinet, where the tenant may run cable outside its space (usually only in the building's pathways, labeled and fire-stopped), and who lets the tenant's contractor into the MDF. Our article on what a low-voltage scope of work should cover lists the line items for each side.
Permits and approvals
Whether a permit applies depends on the scope and the building. We check during the site visit and say what applies before work is scheduled. In a landmarked building or historic district, exterior work may still need Landmarks Preservation Commission approval.
05Cameras, entry and intercoms across use types
The security systems follow the same split. Base building cameras cover what the building answers for: the lobby, the package room, corridors, stairs, the elevator cab, the cellar and roof doors and the sidewalk at the residential entrance. Cameras in residential corridors watch the corridor and the stair doors, not into apartments. Each store and office covers its own space with its own system. When a tenant needs footage from a building camera, such as the sidewalk in front of its store, the managing agent exports the clip on request instead of giving the tenant a login to the building's recorder. See security cameras for mixed-use buildings and our general security camera installation page.
Most mixed-use buildings give the apartments their own lobby and give each store its own street door. An office tenant upstairs either shares the lobby, with its staff on the building's access system and its visitors calling the office from the lobby panel, or gets an entrance of its own. Deliveries are where the uses collide: packages for 48 apartments and stock for two stores. A package room on the building's access system, and a separate delivery path for the stores where the building allows one, keep store deliveries out of the residential lobby. We pick the lock for each door around its use and the building's fire and life safety requirements. A magnetic lock needs a free way out from inside at all times.
The lobby panel is the one device every use touches. In a new building it is usually a network intercom that calls apartments on the residents' phones or in-unit stations, and it can call the office reception if that was planned. See intercoms for mixed-use buildings and access control for co-ops and condos.
06Phased occupancy and tenant turnover
New mixed-use buildings rarely fill at once. The apartments may close while a store sits empty, or the office floor may wait a year for a tenant. The base building systems and the apartment cabling should be complete at turnover. For each empty tenant space the developer leaves the way in finished: the backboard mounted and labeled, the sleeve in place with a pull string, power for the tenant's cabinet, and the carrier's line run to the backboard where the provider allows it. The next tenant then starts from a labeled point instead of a hole in a slab.
Tenants also leave. When a store turns over, its cable is removed or labeled and handed to the next tenant, its sleeves are resealed, and its credentials on the building's doors are removed. That last step is easy to forget when the tenant's own access system leaves with the tenant but the building's reader at the rear door stays.
Questions to settle before the slabs are poured
- Where is the MDF, and is it clear of water lines and of any area that floods?
- Does each owner have its own backboard or rack, and can the base building racks be locked apart from the rest?
- How many sleeves does each pathway get, sized from a cable count, with spares?
- Home runs from the cellar or a closet on each floor, and does every copper run stay within 90 m?
- Which networks are separate, and who controls each switch?
- Where are the five handoff points, and whose contract names each one?
- What does each tenant's work letter give it: backboard, sleeve, carrier line, power?
- What will the building receive at turnover: drawings, test results, the device list and every account?
For what a low-voltage contractor does on a job like this and where the electrician takes over, see what a low-voltage contractor does.
07Mixed-use low-voltage FAQ
Who installs security systems in NYC co-ops, condos and multi-tenant buildings?
In a new building, the developer's low-voltage contractor installs the base building systems: the entry intercom, common-area cameras and access control on the building doors. After turnover, the board or landlord hires a contractor to service and expand them, and each commercial tenant hires its own for its space. We install cameras, access control, intercoms and cabling in co-ops, condos and mixed-use buildings in NYC with our own crew.
What are the MDF and IDFs in a mixed-use building?
The MDF, or main distribution frame, is the building's main telecom room, usually in the cellar near where the carriers enter, and it holds each owner's backboard or rack. IDFs are smaller closets on upper floors, fed from the MDF by fiber or copper, that serve the cable runs on their floors. A mid-rise building can run every apartment home to the MDF; a taller one, or one with long floors, usually needs IDFs to keep copper runs within 90 m.
Should retail tenants share the building's network?
No. Each store should have its own network and its own internet service, apart from the building's cameras and door controllers and from the other tenants. A store that takes payment cards also answers to the card industry's security standard, and keeping its card systems on their own network shrinks what that standard covers. Where a store and the building must connect, such as a rear door on the building's access system, that link is designed and written into both scopes.
Does a mixed-use building need an intercom?
Under New York's Multiple Dwelling Law, section 50-a, an apartment building with eight or more apartments built or converted after 1968 needs self-closing, self-locking entrance doors and an intercom that lets residents talk with visitors and release the door. The residential part of a mixed-use building is usually covered. This is general information, not legal advice; your architect or attorney can confirm what applies to your building.
Who pays for the low-voltage work in a mixed-use building?
Usually the developer pays for the base building systems, the MDF, the risers and the cable to each apartment, and each commercial tenant pays for the work inside its own space. The lease and its work letter set the line for each tenant, including whether the landlord provides the tenant's sleeve, backboard and power. Write it down item by item, because anything the work letter leaves out turns into a negotiation later.
Does low-voltage work in a mixed-use building need a permit?
Whether a permit applies depends on the scope and the building. We check during the site visit and say what applies before work is scheduled. In a landmarked building or historic district, exterior work may still need Landmarks Preservation Commission approval.
Sources and standards
- ANSI/TIA-568 seriesCommercial building cabling: the 90 m permanent link and the 100 m channel.
- ANSI/TIA-569Telecommunications pathways and spaces: equipment rooms, telecommunications rooms, riser sleeves and slots.
- ANSI/TIA-570Residential telecommunications infrastructure, including the distribution device in each unit and cabling in multi-dwelling buildings.
- ANSI/TIA-606 and TIA-607Labeling and administration; bonding and grounding for telecommunications.
- NFPA 70, National Electrical CodeChapter 9, Table 1: 40 percent fill for three or more cables in a raceway. Article 800: communications cable types, including riser (CMR) and plenum (CMP). Sections 300.21 and 800.26: penetrations and the spread of fire.
- New York Multiple Dwelling Law, section 50-aSelf-closing, self-locking entrance doors, and an intercom in buildings of eight or more apartments erected or converted after January 1, 1968.
- PCI DSS v4.0Payment Card Industry Data Security Standard: scope of assessment and network segmentation.
Have a project in mind?
Send us the drawings or the address and tell us what stage the building is at. Same-day quotes when we can.