PoE budget calculator

Enter a PoE switch and the cameras and devices on it: this works out whether its PoE budget powers every device on the worst night, counted by class or by measured draw, and the switch the list needs.

Examples from our guides

The switch

Example switches

Port standard

Each port gives up to 30 W at the port, 25.5 W at the device, Class 4 at most.

The switch counts

Conditions

Devices on the switchcount

Class 2, holds 7 W, draws 4.5 W on a cold night
Class 3, holds 15.4 W, draws 8 W on a cold night
Class 4, holds 30 W, draws 24 W on a cold night
Class 3 holds 15.4 W at the port
Class 4 holds 30 W at the port

Camera draws are examples measured at the port for this kind of camera, not data sheet figures. For any other PoE device, such as an intercom door station, a door controller or an access point, use Other device with its class and its worst-hour draw.

Why 20 percent: the standard sets no margin. About 20 percent is a common planning figure: room for a camera added next year, a heater on a cold night and some aging in the switch power supply.

Class power: IEEE 802.3 class maximums at the port. Class 1 4.0 W, Class 2 7.0 W, Class 3 15.4 W, Class 4 30 W, Class 5 to 8 45, 60, 75 and 90 W. Class 0 is a device that announces no class: 15.4 W.

Port too small: a device whose class is above what the port gives is held to the port maximum. An 802.3af port treats a Class 4 camera as Class 0: 15.4 W at the port, 12.95 W at the camera.

Headroom, counted by class

Over by 44.4 W

2 devices get no power

2 devices get no power. Counted by class, the devices need 164.4 W from a 120 W budget.

An estimate from the inputs above; a site survey sets the real numbers.

POESWITCHBUDGETPOE BUDGET, AS THE SWITCH COUNTS
  • Indoor dome, Class 2
  • Bullet with IR, Class 3
  • PTZ with heater, Class 4
  • No power
16-port switch, 802.3at ports. Ports fill in order; when the budget runs out the last ports stay dark, where a real switch follows its port priority settings.
Ports used
13 of 16
Reserved by class
164.4 W
6 × 7 W + 6 × 15.4 W + 1 × 30 W = 164.4 W
Measured draw, cold night, heater on
99 W
6 × 4.5 W + 6 × 8 W + 1 × 24 W = 99 W
A switch that fits this list

At least 13 PoE ports, 802.3at (PoE+) or higher, and 205.5 W of PoE budget counted by class, which keeps 20 percent spare.

Cold night draw of every device: 99 W. That is the PoE part of the UPS load.

Carry it to the UPS runtime calculator

The math with your numbers

  1. Ports13 devices, 16 PoE ports: every device has a port.
  2. Reserved by class (each device holds its class maximum at the port)6 × 7 W + 6 × 15.4 W + 1 × 30 W = 164.4 W
  3. Measured draw on a cold night with heaters on6 × 4.5 W + 6 × 8 W + 1 × 24 W = 99 W
  4. As the switch counts (by class), powered in port order119 W powered of a 120 W budget; 2 devices asking for 45.4 W get no power.
  5. Planning line120 W × (1 minus 20 percent) = 96 W
  6. Switch that fits every deviceReserved by class, every device: 164.4 W ÷ 0.80 = 205.5 W of PoE budget, 13 ports or more, 802.3at ports or higher.
  7. For the UPSCold night draw of every device: 99 W. Add the switch's own power in the UPS calculator.
Embed this calculator on your site

Paste this where the calculator should appear. It loads the calculator on its own, with a small credit link back to this page.

<iframe src="https://senecasecurity.com/tools/poe-budget-calculator/embed/" title="PoE budget calculator" width="100%" height="1270" style="border:0" loading="lazy"></iframe>
<p><a href="https://senecasecurity.com/tools/poe-budget-calculator/">PoE budget calculator</a> by Seneca Security</p>

How to use the PoE budget calculator

  1. Enter the switch. The number of PoE ports, the PoE budget in watts from its data sheet, and the port standard: 802.3af, 802.3at (PoE+) or 802.3bt.
  2. Set how it counts. Many managed switches can reserve by class or count measured draw. If you do not know which, use By class.
  3. Add the devices. The camera types carry example draws; for anything else, use Other device with its class and worst-hour draw.
  4. Pick the conditions. Cold night, with infrared and heaters on, is the worst hour of the year for outdoor cameras.
  5. Read the headroom, then the switch that fits, and carry the cold night draw to the UPS calculator.

How the PoE budget is worked out

A PoE switch has two limits at once: each port is limited by its standard (15.4 W on 802.3af, 30 W on 802.3at, 60 or 90 W on 802.3bt), and all the ports together by the PoE budget, which is set by the power supply and is usually far less than the port count times 30 W.

Counted by class, the switch reserves each device's class maximum the moment it powers up: 7.0 W for a Class 2 dome even if it draws 3.5 W. Counted by measured draw, it adds up what the devices actually pull, which leaves more room but moves with the weather. The calculator powers devices in port order until the budget runs out, as the budget figure in our PoE guide does.

needed = sum of (count × watts per device)

watts per device = class maximum, or measured draw

headroom = PoE budget minus needed

switch that fits = needed ÷ (1 minus spare margin)

Class maximums come from IEEE 802.3 Clause 33 and Clause 145. The 20 percent margin is a planning figure, not part of the standard.

Worked example: 13 cameras on a 120 W switch

The first example is the four-story mixed-use building in Jersey City from our PoE guide: 6 indoor domes, 6 bullets with infrared and 1 PTZ camera with a heater, on a 16-port PoE+ switch with a 120 W budget. Counted by class, the domes reserve 6 × 7 = 42 W and the first five bullets 5 × 15.4 = 77 W, which leaves 1 W. The sixth bullet and the PTZ never get power, though the whole list draws only 6 × 4.5 + 6 × 8 + 24 = 99 W on a cold night.

Counted by measured draw, every camera runs, but at 99 W the switch is at 82.5 percent of its budget with 21 W to spare, past the 80 percent planning line. Counted by class with 20 percent spare, the list needs 164.4 ÷ 0.8 = 205.5 W, which the 250 W example clears.

Typical PoE values

PoE standards, IEEE 802.3
StandardAt the switch portAt the devicePairs
802.3af (PoE)15.4 W12.95 W2
802.3at (PoE+)30 W25.5 W2
802.3bt Type 360 W51 W4
802.3bt Type 490 W71.3 W4
Example camera draws at the port, typical
CameraClass (reserves)DayNight, IR onCold night
Indoor dome2 (7.0 W)3.5 W4.5 W4.5 W
Bullet with IR3 (15.4 W)5 W8 W8 W
PTZ with heater4 (30 W)14 W18 W24 W

Camera draws are typical examples measured at the port for each kind of camera, not data sheet figures. The data sheet lists the class; the switch's PoE status page shows the real draw.

Common PoE budget mistakes

PoE budget calculator FAQ

How do I calculate a PoE budget?

Add up what each device needs at the switch port: its class maximum if the switch reserves power by class, or its measured worst-hour draw if the switch counts by draw. Compare the total with the PoE budget on the switch data sheet and keep about 20 percent spare.

How many PoE cameras can one switch power?

Divide the PoE budget by what each camera needs at its worst hour, then check that there are enough ports. Counted by class with nothing spare, a 120 W budget covers 17 Class 2 cameras at 7.0 W each but only 7 Class 3 cameras at 15.4 W, whatever the port count.

What is the PoE budget of a switch?

It is the total power the switch can send to all of its PoE ports at once, set by its power supply and listed in watts on the data sheet. It is usually far less than the port count times the port maximum. A 16-port PoE+ switch with a 120 W budget can power 16 cameras that draw 7 W each, not 16 that need 30 W each.

Should a PoE switch count power by class or by measured draw?

Counting by class holds each device's full class power, so nothing loses power when the heaters come on, but the budget fills fast. Counting by measured draw fits more devices on the same budget, but the total moves with the weather, so size it for the coldest night. Either way, set port priority so the most important cameras keep power first.

Does a PoE switch need a UPS?

Every PoE camera goes dark the moment its switch does, so a switch that powers cameras belongs on a UPS together with the recorder. The UPS load is the switch's own power plus the PoE it sends, using the measured draw rather than the class reservations. The UPS runtime calculator takes the cold night draw from this page.